Skip to main content

UPGRADE DISTRIBUTION BOX (DB) FOR ELECTRICAL SYSTEM IN THE HOUSE

Salam all, this work done many months ago. But, only managed to share it in here now.


ISSUE ON THE OLD DB?

Old DB system only consist 1 elcb to accomodate all mcd going into end ciruit. This includes both Permanent (Lighting circuit and other permanent appliances) and portable (power circuit-Socket outlet) circuit. Picture below shows (Fig X) our old DB arrangement for our house electrical system, where protection device are allocated for each end circuit..

Fig 1: Old DB

Additionally, protection devices on old DB also not properly arranged in order which causing a concern interm of safety and upgradability. Usually, DB system arrange in the order of Main switch, ELCB, MCB for lighting and MCB for power circuit.

Fig 2: Old Single line diagram and DB arrangement

ADDITIONAL LOAD REQUIREMENT

However, as we plan to add more load in the system, 3 more Air Conditioning unit and 2 water heater, 1 circuit for Surveilance supply system and 1 circuit for cooker point and dryer. Therefore, the space in the old DB are not enough to accomodate the number of MCB breaker due to added load. About 7 additional breaker are required, with 1 extra ELCB to accomodate separate end circuit between permanent and temporary (portable) circuit


SURUHANJAYA TENAGA GUIDELINES?

Plus, Old DB system only has 1 ELCB, which not follow the Suruhanjaya Tenaga (ST) guideline as on the Table 1. Therefor, new DB are required to accomodate all the additional protection devices and load and new single line diagram are design and drafted following the guide from ST.

Table 1: ST guideline on the Earth Leakage Protection Device [1]

As the number of load increase in the our electrical system, thus upgrading the electrical system are also required to accomodate larger loading no.


DESIGN PROCESS?

Work is started by basic design with total load for all appliances and devices in the house are added together. From the total load, then both ELCB  sizing for permanent circuit and portable circuit can be estimated based on the estimated current going through each ELCB. In this case, estimated value of ELCB shown in Table 2 below. From the total load (total current from permanent circuit and portable circuit) as well, 

Main Swicth sizing can also be calculated from the total current passing both ELCB, as shown in Table 2. All these maximum current value are selected from topping up 30%-40% from estimated current. For example, if calculated current passing through ELCB 1 is 24A, then 30% can be added to this value to get nearest possible protection device. In this case, 40A ELCB are enough to protect the circuit from overload current.

Table 2: Estimated value of Main switch and ELCB


NEW SINGLE LINE DIAGRAM

From the value obtained above, new single line diagram are drafted and shown below (Fig 3). All MCB value are estimated as below based on the total current. Full calculation guide can be download in [1]

Fig 3: New Single Line Diagram




INSTALLATION WORK?

New DB installation procees requires several important parts and tools which need to be purchased or ready in advance, before work can be start (Fig 4).

Fig 4: DB box, Protection devices and arrangement


As most of the upgarde are for Air conditioning unit and Water Heater unit, Therefor, 4mm2 size pure copper cable are purchased as in Fig 5. Each cable cost around RM215, totaled around RM645 just for cable. remaining devices are 40A ELCB with 30mA sensitivity, various current value of MCB breaker.

Fig 5: 4mm2 Pure Copper Cable for wiring


FINAL RESULT?

After around 7 hours of work, alone, the final result shows in the Fig 6 below. Additional kWh meter are also added to the DB box to provides important information, such as total current, and total kWh. These critical information can provde better understanding on the electrical consumption usage, which in turn, could give better idea on how electrical consumption improvement can be done on the later stages.



Fig 6: New DB installed

Thank you for reading and have a good day


REFERENCES:








Comments

Popular posts from this blog

HONDA RS150 TPS: RPM TAK STABIL BILA NOT ON THROTTLE DAN PENYELESAIANNYA

Assalamualaikum dan salam sejahtera Isu TPS ni berlaku pada tahun lepas, Ogos 2020 (milage dalam 24000km, baru dua tahun pakai) sewaktu saya on the way ke KL Masa tu tunggang motor full throttle yang menyebabkan RPM nya selalu mencecah ke CUT-OFF (utk makluman, honda RS150 saya ni tak guna ECU custom, masih guna yang standard). Jadi saya perasan, bila selalu tunggang pada RPM yang sampai CUTT-OFF, ini menyebabkan kesan tak baik pada TPS..jadi utk yang belum jadi problem TPS ni..boleh la cepat ganti ECU ke ECU yang tanpa cutoff. APA TU TPS? TPS bermaksud Throttle positioning sensor..bahasa mudahnya alat ni bertujuan untuk mengesan kedudukan throttle body valve dimana udara masuk ke enjin untuk pembakaran. Dengan itu, baru la ECU tahu berapa banyak bahan bakar yang perlu utk pembakaran berdasarkan bukaan valve tu.  Bila TPS dah problem, TPS akan memberi maklumat yang salah pada ECU berkenaan besar mana valve tu buka, jadi nisbah bahan api dan udara jadi tak betul la. maka, tu yang jadi s

HONDA RS150 IACV: IACV PROBLEM? RPM NAIK TINGGI BILA HIDUPKAN ENJIN?

 Hi semua, Salam sejahtera Masalah IACV saya berlaku selepas isu TPS wujud di milage 24000+km..kemungkinan kedua2nya ini saling berkait. Masalah IACV hadir ketika saya on the way balik semula ke Johor, ketika bahan bakar berkurang dari tangki moto. SIMPTOM  ? bila hidupkan enjin honda RS150 saya, RPM akan naik tinggi dan kadang2 sukar dikawal. tengah jalan pun, jika stop di trafik light, rpm akan naik tinggi dan mengaum bising..so, isu ni biasanya disebabkan IACV IACV APA TU IACV? IACV bermaksud Idle Air Control Valve. bahasa mudahnya nak control udara masuk ke ruang pembakaran sewaktu motosikal kita idle (tanpa pulas pendikit atau throttle) iaitu semasa tak bergerak. FUngsi dia mcm choke la pada motor lama yg guna karburator supaya moto mudah di hidupkan dan dalam masa sama injap dikawal dan dikecilkan bila enjin motosikal telah panas. IACV idling control valve (anak panah, lubang udara yang dikawal) APA FUNGSI IACV? Jika kita dah pulas throttle, IACV dah tak digunakan dan valve udara

HONDA RS150: MAINTENANCE SCHEDULES & MOST COMMON SERVICE WORK

Hi all, this is based on the guide book supplied with your motorcycle when you purchased your motorcycle. With this guide table, hopefully, easy for all, planning their motorcycle service. for me, its really useful since I'm doing my RS150 maintenance myself. The list below shows the most common maintenance schedule and what I did for my RS150 (already 22000+km after almost 9 months): Engine oil change, Petronas Sprinta F700: replace every 1600km Oil strainer: clean every 12000km Spark plug: replace every 12000km (can replace with a high-performance spark plug to reduce maintenance frequency) Fuel filter: replace every 18000km Coolant fluid: replace every 12000km following oil strainer clean work Below are is the maintenance schedule from the guide book. Hope this sharing help